The Atival 312 is an extremely powerful inverter from Schneider Electric with a power range of 0.18 to 15kW. It also supports various industrial control methods.
Today thelivingchristmascompany.com would like to write a tutorial for you to use MicroLogix 1100 PLC to control Schneider ATV312 via “Modbus RTU” RS 485
Micrologix 1100 & Schneider ATV312 “Wiring”

Schneider ATV312 Modbus RTU Settings
In addition to the basic parameters of the inverter, we need to set the communication parameters as follows:
- “CON” Menu
+ Add: 1 (Slave Address= 1)
+ tbr: 9.6 (Baudrate = 9600bps)
+ tF0: 8E1
+ tt0: 3.0 (Comm. timer check Error)
- “CtL” Menu
+ LAC: L3
+ Fr1: Mdb (Modbus)
+ Fr2: Mbd
+ CHCF: SEP
+ Cd1: Mbd
+Cd2: Mbd
Register for Control

Note: MicroLogix 1100 Address = “VFD Address (Dec) + 1“
>>> Motor Control Address = 8501 + 1 = 8502
+ Set Word 8502 = 128 : VFD Fault Reset
= 6 : VFD System Start
= 15 : Motor Forward Run
= 2063 : Motor Reverse Run
= 4111 : Stop
>>> Frequency Reference Address = 8052 + 1 = 8053
Register for Monitoring

- Output Frequency Address = 3202 + 1 = 3203
MicroLogix 1100 Programming
+ Channel Configuration

+ Auto Read/Write Distribution

+ Control Command

+ Set Frequency Command

+ Read Data Response Command

Project Videl Tutorial
======
Documents Reference
- ATV312 Schneider
Password Extract: thelivingchristmascompany.com
Please comment and share the article to the community if you find it useful.
Thanks and Best Regards!
software required for schenider
M241
i will buy PLC M241 sir