Hello friends, in previous posts thelivingchristmascompany.com guided you to use PLC MicroLogix 1100 connected with many types of inverters of different brands.
Today thelivingchristmascompany.com would like to continue sharing the article on how to connect MicroLogix Controller Omron E5CC via Modbus RTU RS485
MicroLogix 1100 & Omron E5CC “Wiring Diagram”
Note: That if the communication distance is >50m, a 120Ω Resistor must be used

E5CC Communication Configuration
Table of communication parameters and configuration in the project

Omron E5CC Register Address

Note: MicroLogix 1100 Address = “VFD Address (Dec) + 1“
- Set Temperature Address = 2103 (hex) + 1
= 8451 (dec) + 1 = 8452
- Read Temperature Present Address = 2000 (hex) + 1
= 8192 (dec) + 1 = 8193
MicroLogix 1100 Programming
+ Channel 0 Configuration

+ Auto Read/Write Distribution

+ Read / Write Command

+ E5CC 1 SV Write Commnad

+ E5CC 2 SV Write Command

+ E5CC 1 Read Command

+ E5CC 2 Read Command

Project Video Tutorial
======
Document Reference
Password Extract: thelivingchristmascompany.com
If you have any difficulty in connecting MicroLogix 1100 with Omron E5CC, please comment below the article, thelivingchristmascompany.com will answer you as soon as I read it.
Best Regards!
i have fialed to get password
password: thelivingchristmascompany.com
tried to connect the ml1100 to a west 6100 temperature controller via modbus rtu
i will make tutorial when i have this