Drives Inverters Guides PLC Guides

Fuji Frenic “Modbus RTU” via Modbus Poll

Hi everybody. In previous posts thelivingchristmascompany.com used some PLCs, HMIs to control FUJI-Frenic Series inverters via Modbus-RTU. Today I will continue to guide you to use your PC to control it.

I use USB to RS485 Cable and “Modbus Poll” software to make this project. You can download the software at the end of the article.

Fuji Frenic & PC Wiring Diagram

You connect according to the diagram below, pay attention if the communication distance is long, you need to use a terminal resistor 120Ω

Fuji Frenic Communication Configuration

Below are the communication parameters to be configured:

  • H30 = 3 ( Motor Control via RS485)
  • Y01 = 1 ( Address No.1)
  • Y02 = 0
  • Y03 = 2
  • Y04 = 2 (baud rate 9600bps)
  • Y05 = 0 (8bit)
  • Y06 = 1 (Even)
  • Y07 = 1 (stop bit = 1)
  • Y10 = 0 (Modbus RTU Selection)
  • Y99 = 0

Modbus Address Area

Below is the table of Hexa addresses corresponding to the Parameters Group

Register Control

>>> Frequency Reference = S (07H) + 05 = 705 (Hex)

>>> Operation Command = S (07H) + 06 = 706 (Hex)
+ Set 706 = 1 >>> Run Forward
+ Set 706 = 2 >>> Run Reverse
+ Set 706 = 0 >>> Stop Run

Register Monitoring

>>> Output Frequency = M (08H) + 09 = 809 (Hex)

>>> Input Power = 80A (Hex)

>>> Output Current = 80B (Hex)

>>> Output Voltage = 80C (Hex)

Modbus Poll Programming

+ Motor Control Word

+ Frequency Setting Command

+ Read Data Monitoring

Detailed Instruction Video

======

Software & Documents Download:
  • (Password Extract: thelivingchristmascompany.com)

If you have any difficulties in connecting Fuji Frenic to PC or have any questions to answer, please comment below the article.

Best Regards!